ING Bank’s main data center in Bucharest, Romania, was severely damaged over the weekend during a fire extinguishing test. In what is a very rare but known phenomenon, it was the loud sound of inert gas being released that destroyed dozens of hard drives. The site is currently offline and the bank relies solely on its backup data center, located within a couple of miles’ proximity.
“The drill went as designed, but we had collateral damage”, ING’s spokeswoman said…
The purpose of the drill was to see how the data center’s fire suppression system worked. Data centers typically rely on inert gas to protect the equipment in the event of a fire, as the substance does not chemically damage electronics…The gas is stored in cylinders, and is released at high velocity out of nozzles uniformly spread across the data center.
According to people familiar with the system, the pressure at ING Bank’s data center was higher than expected, and produced a loud sound – think about the noise a steam engine releases – The bank monitored the sound and it was very loud, a source familiar with the system told us. “It was as high as their equipment could monitor, over 130dB”.
Sound means vibration, and this is what damaged the hard drives. The HDD cases started to vibrate, and the vibration was transmitted to the read/write heads, causing them to go off the data tracks.
In ING Bank’s case, it was “like putting a storage system next to a [running] jet engine,”…
The Bank said it required 10 hours to restart its operation due to the magnitude and the complexity of the damage…Over the next few weeks, every single piece of equipment will need to be assessed. ING Bank’s main data center is compromised “for the most part”…
A catastrophic failover to the backup data center. That’s a helluva noise.